Conduit Fill Calculator (EMT + THHN)

Home / Calculators / Conduit Fill Calculator

Conduit Fill Calculator (EMT + THHN)

By the Trade Template Co. desk · Free, no sign-up · 2026

Pick an EMT conduit size, a THHN wire size, and the number of conductors, and this tool computes your fill percentage against the NEC Chapter 9 fill limits.

Conduit Fill Calculator

Updates instantly as you change any field.

0.0 % fill
40% allowable max
PASSfill status

Real-world edge case? Ask The Board · Find a local pro

Fill limits (NEC Chapter 9, Table 1): 1 conductor = 53%, 2 conductors = 31%, 3 or more conductors = 40% of the conduit’s internal area.

Simplified starting point for planning. Does not apply every NEC adjustment/derating factor. Verify against the current NEC and your local AHJ before installing.

Powered by Trade Template Co.

How conduit fill is calculated

Each wire size has a cross-sectional area (THHN insulation), and each conduit size has a total internal area. Fill percentage is the sum of the wire areas divided by the conduit’s internal area — and it cannot exceed the NEC limit for the wire count.

StepExample: 3/4″ EMT, four 10 AWG THHN
THHN area, 10 AWG0.0211 in² each
Total wire area (4 conductors)4 × 0.0211 = 0.0844 in²
3/4″ EMT internal area0.533 in²
Allowable area (40% limit, 3+ wires)0.533 × 0.40 = 0.2132 in²
Fill percentage0.0844 ÷ 0.533 × 100 = 15.8% — PASS

Fill limits step down as conductor count goes up: a single conductor can fill up to 53% of a conduit (it needs room to be pulled straight), two conductors are capped at 31%, and three or more are capped at 40% to leave room for heat dissipation and pulling.

Do the money side too

Contractor Estimate Calculator (Excel & Google Sheets)

Turn conduit and wire runs into a priced, itemized estimate — materials, labor, and markup, auto-totaled.

More electrician tools

TTC

Trade Template Co. builds back-office tools for trade businesses. This calculator is a simplified planning aid, not a code compliance tool — always confirm fill limits with the current NEC and your local AHJ.

Your Electrician Portal

Every tool, the community, and the code — in one place.

Back to the Electrician Portal

Frequently asked questions

Why does the fill limit change with the number of conductors?

A single conductor needs more relative room to be pulled without jamming, so it is allowed up to 53% fill. Two conductors are capped at 31%, and three or more are capped at 40% — the standard NEC Chapter 9 limits that also protect against heat buildup.

Does this include ground wires?

Include every current-carrying and grounding conductor you plan to pull through the conduit in the conductor count for an accurate fill percentage.

What happens if I exceed the fill limit?

Overfilled conduit makes pulling wire difficult or impossible and can cause overheating. Step up to the next conduit size, or split the run across two conduits.

Is this conduit fill calculator free?

Yes — free, no sign-up. Pick your conduit size, wire size, and conductor count, and read the fill percentage instantly. Estimates only; confirm against the current NEC and your local AHJ.

Ask The Board