HVAC & Mechanical Code Quick-Reference (Plain English, IMC & UMC)

Home / HVAC Contractors / HVAC & Mechanical Code Quick-Reference

HVAC & Mechanical Code Quick-Reference (Plain English, IMC & UMC)

By the Trade Template Co. desk · Searchable, free, no sign-up · 2026
Reference only, not code text or legal advice

These are plain-English summaries for quick recall — not code text. Mechanical rules differ between the International Mechanical Code (IMC) and the Uniform Mechanical Code (UMC), and fuel-gas rules differ between the IFGC and NFPA 54; local amendments and AHJ requirements vary and change. Section numbers are shown at the chapter/topic level as a pointer, not a citation. Always verify against the mechanical and fuel-gas codes currently adopted in your jurisdiction, and size equipment with a full ACCA Manual J load calculation — never a rule of thumb alone.

This is a comprehensive plain-English index to the HVAC and mechanical provisions trades look up most — from combustion air, venting categories, and condensate protection to ductwork, ventilation and exhaust rates, refrigerant handling, gas piping, boilers, and the electrical rules for HVAC equipment. Search by keyword, tap a popular lookup, or filter by category to jump to the plain-English summary and the rule-of-thumb you actually use in the field. Where the IMC and UMC (or the IFGC and NFPA 54) differ, that is noted — always confirm the exact number against your adopted code and local AHJ.

Popular lookups
Showing 173 of 173 rules
IMC 106 / UMC 103
General & Definitions

Permit before mechanical work

Installing, replacing, or relocating most mechanical equipment needs a permit and inspection; a straight like-for-like filter or thermostat swap usually does not, but a system changeout does.

Rule of thumbChangeouts, new gas lines, new ductwork and relocations get a permit – pull it before you cut in.
IMC 302 / UMC 301
General & Definitions

Listed and labeled equipment

Appliances, vents, dampers and controls must be listed and labeled to a recognized standard so the inspector can confirm they are approved for the use.

Rule of thumbNo listing mark, no install – the label is what makes it code-legal.
Manufacturer instructions
General & Definitions

Install per manufacturer instructions

Listed equipment must be installed per the manufacturer’s printed instructions, which are enforceable as part of the listing; where they are stricter than code, the stricter rule governs.

Rule of thumbKeep the instruction sheet on the job – clearances and venting on it are code, not suggestions.
IMC 303 / UMC 303
General & Definitions

Equipment location and protection

Equipment must be located so it is accessible, protected from physical and vehicle damage, and not exposed to the weather unless it is listed for outdoor use.

Rule of thumbAdd a bollard or curb anywhere a unit can get hit by a vehicle or door.
IMC 304 / UMC 304
General & Definitions

Access and working clearance, general

Every appliance needs enough clearance for service, inspection, and removal, and clearances to combustibles must match the listing or the reduced-clearance tables.

Rule of thumbIf you cannot pull the burner or coil without moving the unit, you do not have code clearance.
IMC 301.15 / listing
General & Definitions

Clearance to combustibles

Maintain the listed clearance from the appliance and its vent to wood, drywall paper, and other combustibles, or use an approved reduced-clearance assembly.

Rule of thumbReduced clearances need a listed shield with an air gap – a bare sheet of metal on the wall is not it.
IMC 306 / UMC 304
General & Definitions

Appliances must remain accessible

Appliances cannot be walled in or buried behind fixed construction; you must be able to reach them for service and eventual replacement.

Rule of thumbLeave a real path and a real opening – not a hole a service tech has to crawl through the drywall to find.
IMC 401 / UMC 402
General & Definitions

Return of conditioned space by ventilation

Occupied buildings need ventilation air, either natural (operable openings) or mechanical, sized to the occupancy – most homes rely on mechanical whole-house ventilation.

Rule of thumbTight new homes need mechanical fresh air – you cannot count on leaks anymore.
IMC 304.10 / UMC 303
General & Definitions

Appliances in flood zones

In flood-hazard areas, equipment must be elevated above the design flood elevation or be flood-resistant, and located so floodwater will not enter or damage it.

Rule of thumbGet the unit up on a stand above the flood line in flood zones – verify the elevation with the AHJ.
IMC / UMC Ch.1
General & Definitions

IMC vs UMC – know which is adopted

The International Mechanical Code (IMC) with the fuel-gas code (IFGC), and the Uniform Mechanical Code (UMC) with NFPA 54, cover the same ground but differ on specific numbers and methods.

Rule of thumbConfirm which mechanical AND which fuel-gas code your jurisdiction adopted before you quote clearances or sizing.
IMC 306.3 / UMC 304
Equipment Install & Access

Attic equipment access opening

Equipment in an attic needs an access opening large enough to remove the largest component, commonly at least 22 in by 30 in, and no smaller than the equipment.

Rule of thumbFrame the attic hatch to at least 22 x 30 in – and big enough to actually pull the air handler.
IMC 306.3
Equipment Install & Access

Attic passageway and service platform

A continuous solid passageway (commonly 24 in wide, up to about 20 ft long) must lead to a level service platform at least 30 in by 30 in in front of the equipment control side.

Rule of thumbLay a real catwalk to the unit and a 30 x 30 in platform to stand on – no balancing on joists.
IMC 306.4 / UMC 304
Equipment Install & Access

Under-floor (crawlspace) access

Equipment under a floor needs an access opening (commonly 22 in by 30 in) and a passageway with at least 30 in of vertical clearance and a level working space at the controls.

Rule of thumbCrawlspace units still need a 30-in-tall path and a 30 x 30 in work space at the controls.
IMC 306.5
Equipment Install & Access

Equipment on roofs and elevated

Appliances more than 16 ft above grade need permanent access (interior stair or ladder), and rooftop units near a roof edge need a guard or the edge protected within 10 ft.

Rule of thumbTall or rooftop installs need fixed access and edge protection – a portable ladder does not pass.
IMC 306.3.1 / NEC 210.70
Equipment Install & Access

Lighting at attic/under-floor equipment

A luminaire controlled by a switch at the passageway entrance must light the working space at equipment located in an attic or under-floor space.

Rule of thumbPut a light over the unit and the switch at the hatch – required, not optional.
NEC 210.63
Equipment Install & Access

Service receptacle at HVAC equipment

A 125-volt, 15/20-amp receptacle must be within 25 ft of and on the same level as heating, cooling, and refrigeration equipment for service tools.

Rule of thumbA service receptacle within 25 ft of every condenser, furnace, and air handler – not fed from the unit’s own disconnect.
IMC 304.9 / UMC 304
Equipment Install & Access

Clearance for service on all sides

Working space must let a tech service every side that requires access per the listing – typically the front/control side plus room to pull coils, filters, and heat exchangers.

Rule of thumbCheck the nameplate service clearances per side, not just the front.
IMC 303.3
Equipment Install & Access

Prohibited locations for fuel-fired appliances

Fuel-burning appliances are generally not allowed in sleeping rooms, bathrooms, closets, or spaces opening into them, unless they are direct-vent or listed and installed for that location.

Rule of thumbOnly direct-vent or sealed-combustion units belong near bedrooms and baths.
IMC 304.6 / listing
Equipment Install & Access

Appliances in garages – ignition source height

Where fuel-fired or spark-producing equipment is in a garage, place ignition sources so they are elevated (commonly 18 in above the floor) unless the unit is listed as flammable-vapor-ignition-resistant.

Rule of thumbGet the burner or igniter up about 18 in in a garage, or use an FVIR-listed unit; protect it from vehicles.
IMC 304.3
Equipment Install & Access

Anchor equipment against displacement

Equipment must be set level and secured so it cannot shift, tip, or move under normal operation, and per seismic requirements where they apply.

Rule of thumbStrap and anchor the unit – especially water heaters and rooftop gear in seismic zones.
IMC 306.1
Equipment Install & Access

Working space not used for storage

The required service clearance and platform at equipment must be kept clear – it cannot double as storage or be blocked by later construction.

Rule of thumbThe space in front of the furnace is service clearance, not a shelf.
IMC 305 / listing
Equipment Install & Access

Equipment supports and platforms

Suspended or elevated equipment needs supports designed for the load, and combustion or spark sources on the floor of a garage must be elevated per the listing.

Rule of thumbBuild the platform and hangers for the wet, full-of-water weight, not the shipping weight.
IMC 303.4
Equipment Install & Access

Combustion and dilution air not blocked

Do not locate equipment where required combustion, ventilation, or dilution air openings are obstructed by construction, storage, or later finishes.

Rule of thumbKeep louvers and air openings clear – a stored box over a combustion-air grille starves the burner.
IMC 306.2
Equipment Install & Access

Removal without demolition

Access must allow the largest single component (or the whole appliance) to be removed for replacement without cutting into the building structure.

Rule of thumbIf replacing the coil means cutting drywall, the access is undersized.
IMC 301.2 / listing
Equipment Install & Access

Condensing appliance freeze protection

Condensing furnaces and their condensate lines produce water that must be protected from freezing in unconditioned space, or the appliance can shut down or be damaged.

Rule of thumbInsulate or heat-trace condensate in cold attics and crawlspaces – a frozen trap locks the furnace out.
IFGC 304 / NFPA 54 9.3
Combustion Air

Unconfined vs confined space

A space with at least 50 cubic feet per 1,000 BTU/hr of total appliance input is treated as unconfined for combustion air; below that it is a confined space needing engineered openings.

Rule of thumbUnder about 50 cu ft per 1,000 BTU/hr of input, you must add combustion-air openings.
IFGC 304.5
Combustion Air

Confined space – all air from outdoors

A confined space can draw combustion air from outdoors through two openings (one high, one low), each sized to the total input, or a single opening where permitted.

Rule of thumbTwo openings, high and low, straight to outdoors is the reliable way to feed a closet furnace.
IFGC 304.6
Combustion Air

Vertical duct openings – 1 sq in per 4,000 BTU

When outdoor combustion air comes through vertical ducts, each of the two openings is sized at about 1 square inch per 4,000 BTU/hr of total input.

Rule of thumbVertical ducts: roughly 1 sq in per 4,000 BTU/hr each opening.
IFGC 304.6
Combustion Air

Horizontal duct openings – 1 sq in per 2,000 BTU

When outdoor combustion air comes through horizontal ducts, each of the two openings is sized larger, about 1 square inch per 2,000 BTU/hr of total input.

Rule of thumbHorizontal ducts: roughly 1 sq in per 2,000 BTU/hr each opening – double the vertical size.
IFGC 304.6.1
Combustion Air

Single outdoor opening – 1 sq in per 3,000 BTU

One permanent opening direct to outdoors can serve, sized at about 1 square inch per 3,000 BTU/hr, with clearance around the appliance and communication top and bottom of the space.

Rule of thumbSingle opening method: about 1 sq in per 3,000 BTU/hr, with the appliance clear of the walls.
IFGC 304.5.3
Combustion Air

Indoor combustion air from another room

Air can come from an adjoining unconfined interior space through two openings sized about 1 square inch per 1,000 BTU/hr, each at least 100 square inches.

Rule of thumbInterior openings to a big adjacent room: 1 sq in per 1,000 BTU/hr, 100 sq in minimum each.
IFGC 304 / NFPA 54
Combustion Air

Combined interior volume method

Doors, grilles, or openings can combine two rooms so their total volume meets the 50 cu ft per 1,000 BTU/hr test and the space counts as unconfined.

Rule of thumbLouvered doors between rooms can make a confined closet count as part of a larger unconfined space.
IFGC 304.10
Combustion Air

Louver and grille free area

Required opening sizes are net free area; metal louvers pass roughly 75 percent and wood louvers about 25 percent, so size the gross grille up accordingly.

Rule of thumbSize for net free area – a wood louver may need 4x the gross size of the required opening.
IFGC 304.11
Combustion Air

Combustion air openings kept clear

Combustion-air openings and ducts must not be screened so fine that they clog, and cannot be blocked by dampers that close them off during operation.

Rule of thumbCoarse screen only, and no operable damper that can shut the combustion-air path.
IFGC 304.1
Combustion Air

Direct-vent and sealed combustion exempt

Direct-vent (sealed-combustion) appliances draw combustion air through their own listed pipe from outdoors and do not need room combustion-air openings.

Rule of thumbSealed-combustion units feed themselves – no room combustion-air calc needed.
IFGC 304 / mfr
Combustion Air

Known-air-infiltration-rate method

An engineered method using the building’s measured or assumed infiltration rate can be used in tight construction, but it requires calculation and AHJ acceptance.

Rule of thumbTight houses may need the infiltration-rate calc – not a rule of thumb; document it for the AHJ.
IFGC 304 / UMC 701
Combustion Air

Verify code – IFGC vs UMC/NFPA 54 differ

Combustion-air sizing factors and methods differ between the IFGC, NFPA 54, and the UMC; use the exact tables in the fuel-gas code your jurisdiction adopted.

Rule of thumbConfirm the adopted fuel-gas code and its combustion-air tables with the AHJ before final sizing.
IFGC 503 / NFPA 54
Venting & Chimneys

Appliance venting categories I-IV

Gas appliances are Category I (negative pressure, non-condensing), II (negative, condensing), III (positive, non-condensing), or IV (positive, condensing); the vent system must match the category.

Rule of thumbMatch the vent to the category – a Category IV condensing furnace vents in PVC, not B-vent.
IFGC 503
Venting & Chimneys

Category I appliances and Type B / lined masonry

Category I draft-hood and fan-assisted appliances vent through Type B gas vent or a properly lined masonry chimney sized from the NFPA 54 vent tables.

Rule of thumbCategory I gets B-vent or a lined masonry flue sized off the tables – never bare unlined brick.
IFGC 503
Venting & Chimneys

Category IV condensing – listed plastic vent

Category IV condensing appliances use the vent material the manufacturer lists (PVC, CPVC, polypropylene, or special stainless), run to the listed length and fittings.

Rule of thumbUse exactly the plastic or SS vent the furnace lists – mixing brands or exceeding length voids the listing.
IFGC 503
Venting & Chimneys

Type B gas vent basics

Type B double-wall vent serves listed draft-hood and fan-assisted Category I gas appliances only – not oil, not solid fuel, and not high-temperature appliances.

Rule of thumbB-vent is gas-only; oil and wood need Type L or a listed chimney.
IFGC 503 / mfr
Venting & Chimneys

Type L vent for oil and some gas

Type L vent handles oil-fired and listed gas appliances at higher temperatures than B-vent, per the appliance and vent listings.

Rule of thumbOil-fired units generally need Type L or a listed chimney, not B-vent.
IMC 801 / IFGC 503
Venting & Chimneys

Masonry chimney lining required

A masonry chimney serving gas or oil appliances needs an approved liner (clay tile or listed metal) sized to the appliance; unlined or oversized flues cause condensation and spillage.

Rule of thumbReline old masonry chimneys – an oversized, unlined flue will not draft a modern furnace.
IFGC 504
Venting & Chimneys

Vent sizing from the NFPA 54 tables

Vent and connector diameters come from the capacity tables using appliance input, vent height, and lateral length – not a guess or matching the appliance outlet size.

Rule of thumbSize the vent from the tables by input, height, and lateral – the draft-hood collar size is only a starting point.
IFGC 503.6
Venting & Chimneys

Vent connector rise and length

The connector should rise continuously to the vent with limited horizontal length; long flat runs and multiple elbows cut capacity and must be figured into the table sizing.

Rule of thumbKeep connectors short, rising, and with few elbows – every elbow and foot of lateral derates capacity.
IFGC 503.6
Venting & Chimneys

Common venting of two appliances

Two appliances on a common vent use the combined and connector tables; the smaller appliance connector enters above the larger, with proper rise, to avoid spillage.

Rule of thumbOn a common vent, size each connector and the common vent from the tables – do not just tie them together.
IFGC 503
Venting & Chimneys

Orphaned water heater after furnace changeout

When a high-efficiency furnace is added and the water heater is left alone on the old common vent, the now-oversized vent can fail to draft – it must be resized or relined.

Rule of thumbReplacing the furnace? Re-check the water heater vent – an orphaned tank often needs a smaller liner.
IFGC 503.6.6
Venting & Chimneys

Vent terminating above the roof

Type B and masonry vents must extend a minimum height above the roof (commonly at least 12 in, and more based on distance from the ridge and roof pitch) per the termination table.

Rule of thumbTerminate at least 12 in above the roof and per the pitch/ridge table – taller near a steep ridge.
IFGC 503.8
Venting & Chimneys

Mechanical-draft/direct-vent termination clearances

Forced-draft and direct-vent terminals must clear windows, doors, and gravity air inlets (commonly at least 4 ft below, 4 ft horizontally, or 1 ft above within 10 ft) and sit above grade/snow.

Rule of thumbKeep power-vent terminals clear of openings (about 4 ft) and up above expected snow, away from walkways.
IFGC 503.8
Venting & Chimneys

Vent terminal clearance to grade and inlets

Vent terminals must be at least 12 in above grade or above the anticipated snow line, and clearances increase with input rating; keep them away from air intakes.

Rule of thumbAt least 12 in above grade/snow, and farther from any fresh-air intake – verify the exact clearance by input.
IMC 806 / IFGC 503
Venting & Chimneys

Vent connector clearance to combustibles

Single-wall connectors need generous clearance to combustibles (often 6 in or more); double-wall Type B connectors have reduced listed clearances.

Rule of thumbSingle-wall connector: keep 6 in off wood. Tight to framing means double-wall.
IMC 805
Venting & Chimneys

Vent connector support and slope

Connectors must be supported to keep their upward slope (commonly at least 1/4 in per foot), be firmly joined, and not sag into a low spot that traps condensate.

Rule of thumbSlope connectors up at least 1/4 in per foot and support them – no sags or downhill runs.
IMC 801 / listing
Venting & Chimneys

Factory-built chimney (Type HT / solid fuel)

Solid-fuel and high-temperature appliances need a listed factory-built chimney or a code-compliant masonry chimney with the required clearances and termination.

Rule of thumbWood and high-temp appliances need an HT/solid-fuel-rated chimney – not gas B-vent.
IMC 801.18 / IRC
Venting & Chimneys

Chimney 3-2-10 termination rule

A chimney must extend at least 3 ft above the roof at its penetration and at least 2 ft above anything within 10 ft horizontally (the 3-2-10 rule).

Rule of thumb3 ft above the roof, 2 ft above anything within 10 ft – the classic 3-2-10.
IFGC 503.5
Venting & Chimneys

Draft hood and barometric damper

Draft hoods (gas) and barometric dampers (oil) must be installed in the same space as the appliance and not be modified, to protect against downdraft and overfire.

Rule of thumbLeave the draft hood/baro damper as listed and in the appliance room – do not relocate or block it.
IMC 804 / listing
Venting & Chimneys

Do not reduce vent below appliance outlet

The vent connector and vent generally cannot be smaller than the appliance flue outlet unless the sizing tables specifically allow it for that configuration.

Rule of thumbDo not neck a 4-in flue collar down to 3-in vent unless the table says you can.
IFGC 503 / UMC 802
Venting & Chimneys

Verify code – IFGC vs UMC venting differ

Venting tables, categories handling, and termination clearances differ between the IFGC/NFPA 54 and the UMC; size and terminate from the adopted code.

Rule of thumbUse the adopted fuel-gas/mechanical code’s vent tables and terminations – confirm with the AHJ.
IMC 307.2
Condensate

Condensate disposal to approved point

Cooling coil and evaporator condensate must drain to an approved location – an indirect waste with an air gap, a floor drain, or outdoors – never directly to the ground where it causes damage.

Rule of thumbRoute condensate to an approved receptor with an air gap – not onto the roof or slab.
IMC 307.2.1
Condensate

Primary drain size and slope

The primary condensate drain is commonly at least 3/4 in and pitched at least 1/8 in per foot toward the discharge so it drains fully and does not stand.

Rule of thumb3/4 in minimum, pitched at least 1/8 in per foot – no flat or uphill runs.
IMC 307.2.4 / mfr
Condensate

Condensate trap on the drain

A trap is installed on the primary drain per the equipment instructions to overcome the fan pressure (positive or negative) so the pan drains instead of holding water or blowing dry.

Rule of thumbTrap the drain per the manufacturer – depth depends on whether the coil is draw-through or blow-through.
IMC 307.2.3
Condensate

Secondary (auxiliary) drain required

Where a condensate overflow would damage the building, provide an auxiliary drain pan, a separate secondary drain line, or a water-level shutoff device.

Rule of thumbEvery attic and above-ceiling coil needs overflow protection – pick pan, secondary line, or float switch.
IMC 307.2.3
Condensate

Auxiliary drain pan sizing

An auxiliary drain pan must be at least 1-1/2 in deep, extend beyond the equipment (commonly about 3 in on all sides), and drain to a conspicuous point.

Rule of thumbAux pan at least 1-1/2 in deep and 3 in wider than the unit, draining where a homeowner will see it drip.
IMC 307.2.3
Condensate

Float switch / water-level shutoff

A listed water-level detection device can be used instead of a secondary drain, wired to shut the equipment off before the pan overflows.

Rule of thumbA float switch that kills the unit is an accepted alternative to a second drain line.
IMC 307.2.2
Condensate

Secondary drain to conspicuous location

The secondary drain line must discharge where overflow will be noticed (such as over a window or exterior soffit) to signal that the primary drain is plugged.

Rule of thumbTerminate the overflow line where a dripping tells the owner the primary is clogged.
IMC 307.2.5
Condensate

No condensate to sanitary without air gap

Condensate discharged to the sanitary drainage system must have an air gap or approved trap and connection so sewer gas cannot enter and cross-connection is prevented.

Rule of thumbNever hard-pipe condensate into the DWV – use an air gap into a receptor.
IMC 307.2
Condensate

Condensate material and freeze protection

Condensate piping must be approved corrosion-resistant material sized to the load, and protected from freezing where it runs through unconditioned space.

Rule of thumbUse approved pipe and keep condensate from freezing in cold attics – a frozen line backs up the pan.
IMC 307 / UMC 310
Condensate

Verify code – condensate specifics vary

Pan sizes, slope, and secondary-protection options differ slightly between the IMC and UMC and by local amendment; confirm the adopted code and AHJ.

Rule of thumbCheck the adopted code for exact pan depth and overflow rules before final inspection.
IMC 603 / mfr
Ductwork

Duct sizing and friction basics

Ducts are sized to deliver the design airflow at an acceptable friction rate and velocity, typically using ACCA Manual D or equivalent – not just matching the equipment collar.

Rule of thumbSize ducts with Manual D to the design CFM and static, not by eyeballing the takeoff size.
IMC 603.9 / IECC
Ductwork

Duct sealing required

Duct joints, seams, and connections must be sealed with mastic, mastic-plus-mesh, or listed tape; cloth-backed rubber duct tape is not permitted on ductwork.

Rule of thumbSeal every joint with mastic or listed tape – standard ‘duct tape’ fails and does not pass energy code.
IMC 603.4 / SMACNA
Ductwork

Duct support spacing

Sheet-metal and flex ducts must be supported at intervals per the code/SMACNA (metal commonly about every 10 ft; flex more often) with hangers that do not cut or crush the duct.

Rule of thumbSupport metal duct roughly every 10 ft and flex more often – wide straps, no wire cutting into liner.
IMC 602 / IMC 603
Ductwork

Duct materials and classes

Ducts must be listed materials – galvanized steel, aluminum, listed fibrous glass, or factory-made air ducts/connectors listed to UL 181 (Class 0 or Class 1).

Rule of thumbUse listed duct/connector material rated for the system – UL 181 Class 0 or 1 for flex and board.
IMC 603.6 / listing
Ductwork

Flexible duct limits

Flex duct cannot pass through walls, floors, or fire-rated assemblies, must be supported to avoid sag and sharp bends, and is limited in length per the energy code to control friction.

Rule of thumbKeep flex short, straight, and out of walls/floors – long saggy flex kills airflow.
IMC 601.2
Ductwork

Return air – prohibited sources

Return air cannot be taken from closets, bathrooms, toilet rooms, kitchens (commercial), garages, mechanical/furnace rooms, or refrigeration machinery rooms.

Rule of thumbNever pull return from a garage, bath, or the furnace room – contamination and CO risk.
IMC 918 / IRC
Ductwork

Return air path and transfer

Rooms with supply air need a return path back to the equipment (ducted return, transfer grille, or jump duct); closing doors should not starve the return.

Rule of thumbGive every supplied room a return path – a door undercut alone usually is not enough.
IMC 607 / IBC
Ductwork

Fire and smoke dampers at rated assemblies

Ducts penetrating fire-rated walls, floors, and shafts need listed fire dampers, smoke dampers, or combination dampers with access for inspection and reset.

Rule of thumbRated wall or shaft penetration means a listed damper plus an access door to service it.
IMC 607.4
Ductwork

Damper access doors

Every fire/smoke damper must have a labeled access door large enough to inspect, test, and reset the damper.

Rule of thumbNo damper without a marked access panel next to it.
IMC 604 / IECC
Ductwork

Duct insulation

Ducts in unconditioned space must be insulated to the energy-code R-value (commonly R-6 to R-8 depending on climate and location) to limit heat gain and loss.

Rule of thumbInsulate attic and crawlspace ducts to code R-value – uninsulated attic duct bleeds capacity.
IMC 603.10
Ductwork

Under-floor plenum limits

Using an under-floor space as a supply plenum is tightly restricted – specific construction, no gas piping/wiring violations, and it is prohibited by many jurisdictions.

Rule of thumbUnder-floor plenums are heavily restricted or banned – confirm with the AHJ before relying on one.
IMC 602.2
Ductwork

Plenum material and contents

Materials exposed in return-air plenums (including above suspended ceilings) must be low smoke/flame spread, and only permitted items (plenum-rated cable, listed pipe) may be inside.

Rule of thumbOnly plenum-rated cable and listed materials go in a ceiling return plenum.
IMC 603.17 / mfr
Ductwork

Duct connections to equipment

Ducts must connect to equipment with approved fittings and flexible connectors where needed for vibration; connections must be sealed and mechanically secure.

Rule of thumbUse a listed flex connector at the air handler to cut noise – then seal it.
IMC 603.4
Ductwork

Flexible air connectors length limit

Flexible air connectors (as opposed to listed flex duct) are limited in length (commonly about 14 ft) and cannot pass through construction.

Rule of thumbKeep flexible connectors short and out of walls – they are not a substitute for real duct runs.
IMC 605
Ductwork

Air filters upstream of coil

Systems need filters listed and located to protect the coil and be serviceable, with the filter access built into the return or cabinet.

Rule of thumbPut a serviceable filter ahead of every coil – and leave room to change it.
IMC 603.18 / IBC
Ductwork

Duct penetrations firestopped

Duct penetrations of rated and non-rated assemblies must be firestopped or sealed as required, and annular spaces closed.

Rule of thumbFirestop every duct penetration of a rated assembly to keep the rating.
IMC 606 / IBC
Ductwork

Smoke detection and shutdown

Air systems above a threshold airflow (commonly over 2,000 CFM) need duct smoke detectors arranged to shut the unit down and, where required, tie to the fire alarm.

Rule of thumbOver about 2,000 CFM, add duct smoke detection wired to shut the fan down.
IMC 603 / IECC
Ductwork

Building cavities not used as ducts

Framing cavities (stud bays, panned joists) generally cannot serve as supply ducts and are restricted as returns under the energy code because they leak.

Rule of thumbDo not use stud bays as supply ducts – run real, sealed duct.
IMC 603.8
Ductwork

Duct in concrete or underground

Ducts under a slab or in the ground must be listed for that use, corrosion-resistant, and sloped to drain, with attention to condensation and radon/moisture.

Rule of thumbUnderground duct must be listed for it and drain – standard sheet metal will corrode.
IMC 603 / UMC 601
Ductwork

Verify code – duct rules vary

Duct sealing thresholds, support spacing, and plenum rules differ between the IMC, UMC, and the adopted energy code; confirm the local requirements.

Rule of thumbCheck the adopted mechanical and energy codes for exact duct sealing and support numbers.
IRC M1505 / ASHRAE 62.2
Ventilation & Exhaust

Whole-house mechanical ventilation rate

New homes need continuous or intermittent whole-house ventilation sized to roughly 0.03 CFM per square foot plus 7.5 CFM per bedroom-plus-one, per ASHRAE 62.2 / the IRC.

Rule of thumbBallpark 0.03 CFM/sq ft + 7.5 CFM per (bedrooms+1) – then verify against 62.2.
IRC M1505 / IMC 403
Ventilation & Exhaust

Bathroom exhaust rate

Bathrooms need mechanical exhaust of about 50 CFM intermittent or 20 CFM continuous, ducted to the outdoors, unless there is adequate operable window ventilation.

Rule of thumb50 CFM on a switch or 20 CFM continuous per bath – ducted outside, not into the attic.
IRC M1505 / IMC 403
Ventilation & Exhaust

Kitchen exhaust rate (residential)

Residential kitchens need about 100 CFM intermittent or 25 CFM continuous of local exhaust where mechanical exhaust is provided, vented outdoors.

Rule of thumbAbout 100 CFM intermittent for a range hood – and it must terminate outdoors.
IMC 501.2 / IRC
Ventilation & Exhaust

Exhaust must terminate outdoors

Exhaust from bathrooms, kitchens, and dryers must discharge to the outdoors, not into an attic, crawlspace, soffit-only, or other concealed space.

Rule of thumbDump exhaust outside the building envelope – blowing it into the attic causes moisture damage.
IMC 501.3
Ventilation & Exhaust

Exhaust termination clearances

Exhaust outlets must clear property lines, openings into the building, and air intakes (commonly at least 3 ft from openings and 10 ft from intakes, more for contaminated exhaust).

Rule of thumbKeep exhaust terminals at least 3 ft from windows/doors and 10 ft from fresh-air intakes.
IRC M1502 / IMC 504
Ventilation & Exhaust

Dryer exhaust – material and no screen

Clothes dryer exhaust must be rigid or listed semi-rigid smooth-wall metal (not plastic or foil flex), 4 in diameter, with a backdraft damper and no screen at the termination.

Rule of thumbSmooth 4-in metal, backdraft damper, no screen – foil flex in the wall is a fire hazard.
IRC M1502.4
Ventilation & Exhaust

Dryer duct length limit

Dryer exhaust developed length is limited (commonly 35 ft), reduced by elbows (about 2.5 ft per 45 degrees and 5 ft per 90 degrees), unless the dryer listing allows more.

Rule of thumbStart at 35 ft and subtract 5 ft per 90 and 2.5 ft per 45 – or use the booster/listing values.
IRC M1502.4.2
Ventilation & Exhaust

Dryer transition duct

The transition duct from the dryer to the wall must be listed, limited in length (commonly 8 ft), and not concealed in construction.

Rule of thumbListed transition duct, 8 ft max, always exposed – never buried in the wall.
IRC M1502.4.7
Ventilation & Exhaust

Dryer duct length identification

Where the equivalent length exceeds the manufacturer’s default, a permanent label near the dryer connection must state the developed length so future dryers can be matched.

Rule of thumbLabel long dryer runs at the connection so the next dryer gets matched to the duct.
IMC 505 / IRC
Ventilation & Exhaust

Makeup air for large kitchen hoods

Residential range hoods or exhaust exceeding a threshold (commonly 400 CFM) require interlocked makeup air so the exhaust does not depressurize and backdraft combustion appliances.

Rule of thumbOver about 400 CFM of hood exhaust, add interlocked makeup air – or you can backdraft the furnace.
IMC 403 / ASHRAE 62.1
Ventilation & Exhaust

Commercial ventilation rates

Commercial and assembly spaces use per-person and per-area outdoor-air rates from the ventilation-rate procedure (ASHRAE 62.1 / IMC Table 403.3) based on occupancy.

Rule of thumbSize commercial outdoor air from the occupancy table – a classroom and a warehouse are not the same.
IMC 404
Ventilation & Exhaust

Enclosed parking garage exhaust

Enclosed parking and repair garages need mechanical exhaust (commonly about 0.75 CFM per square foot, or CO-sensor controlled) to clear vehicle exhaust.

Rule of thumbAround 0.75 CFM/sq ft for enclosed parking, or CO-controlled fans – verify the current rate.
IMC 502
Ventilation & Exhaust

Contaminant and hazardous exhaust

Spaces handling contaminants (spray booths, battery rooms, labs, repair garages) need dedicated exhaust systems that keep the space negative and discharge safely.

Rule of thumbContaminant sources get their own dedicated, negative-pressure exhaust – do not combine with general HVAC.
IMC 501.4
Ventilation & Exhaust

Exhaust and environmental air duct independence

Environmental exhaust ducts (baths, dryers, hoods) generally cannot connect to gas vents, plumbing vents, or other exhaust systems – each gets its own duct to outdoors.

Rule of thumbOne dedicated duct per exhaust – do not tie a bath fan into a plumbing or gas vent.
IMC 401.4
Ventilation & Exhaust

Outdoor intake opening location

Outdoor-air intakes must be located away from sources of contamination (loading docks, exhausts, plumbing vents, cooling towers) at the required separation distances.

Rule of thumbKeep fresh-air intakes upwind and away from exhausts, vents, and dumpsters.
IMC 401.5
Ventilation & Exhaust

Ventilation air balance and dampers

Mechanical ventilation must provide the required outdoor air, with dampers and controls arranged so the design fresh-air quantity is actually delivered.

Rule of thumbVerify the outdoor-air damper actually opens to the design position – not just that a fan runs.
IMC 918 / IRC
Ventilation & Exhaust

Bath/laundry fan ducted, not just soffit

Exhaust fans must be ducted full-size to a proper exterior termination; discharging into a soffit vent or terminating short causes moisture to recirculate.

Rule of thumbRun the fan duct to a wall/roof cap – a soffit dump just pulls the moisture back in.
IMC 401 / UMC 402
Ventilation & Exhaust

Verify code – ventilation rates vary

Whole-house and commercial ventilation rates differ among the IRC, IMC, UMC, ASHRAE 62.1/62.2 versions, and local energy amendments – use the adopted version.

Rule of thumbConfirm the adopted ventilation standard and edition before finalizing rates – they change with each cycle.
IMC 1101 / ASHRAE 15
Refrigeration & Refrigerant

Refrigeration systems follow ASHRAE 15

Refrigeration and comfort-cooling systems are designed and installed to the mechanical code and ASHRAE 15 for safety, refrigerant limits, and machinery rooms.

Rule of thumbComfort cooling still falls under the refrigerant-safety rules – know the refrigerant and its class.
IMC 1103 / ASHRAE 34
Refrigeration & Refrigerant

Refrigerant safety classification

Refrigerants are classed by toxicity (A lower, B higher) and flammability (1 none, 2L mildly, 2, 3 higher) – for example R-410A is A1 and R-32/R-454B are A2L.

Rule of thumbKnow the class – A2L mildly flammable refrigerants have extra install, storage, and leak-detection rules.
IMC 1104
Refrigeration & Refrigerant

Refrigerant quantity and occupancy limits

The maximum refrigerant charge allowed in an occupied space depends on the refrigerant’s class and the room volume (the refrigerant concentration limit / RCL).

Rule of thumbCheck charge against room volume – a big charge in a small occupied room can exceed the RCL.
IMC 1105 / ASHRAE 15
Refrigeration & Refrigerant

Machinery room requirements

Where charge or refrigerant class requires it, a machinery room with dedicated ventilation, refrigerant detection, and safe relief discharge is required.

Rule of thumbLarge or higher-hazard systems need a code machinery room with detection and mechanical exhaust.
IMC 1105
Refrigeration & Refrigerant

Refrigerant detection and alarm

Machinery rooms and certain systems need refrigerant detectors that alarm and start ventilation at set concentrations, especially for A2L and toxic refrigerants.

Rule of thumbA2L and machinery-room systems need leak detection that triggers the exhaust fan and alarm.
IMC 1106 / ASHRAE 15
Refrigeration & Refrigerant

Pressure-relief discharge

Refrigerant pressure-relief devices must discharge to a safe location (typically outdoors, away from openings and intakes) per the code and manufacturer.

Rule of thumbRoute relief discharge outdoors to a safe point – not into the machinery room or an occupied space.
EPA 608
Refrigeration & Refrigerant

Refrigerant handling and recovery (EPA 608)

Federal law requires EPA Section 608 certification to handle regulated refrigerants, with mandatory recovery (no venting) and proper cylinders for recovered refrigerant.

Rule of thumbNever vent refrigerant – recover it, and only 608-certified techs may open the system.
EPA 608 / A2L
Refrigeration & Refrigerant

A2L handling and equipment

Mildly flammable A2L refrigerants require compatible recovery equipment, leak checks, and adherence to charge limits and ignition-source controls per the equipment listing.

Rule of thumbUse A2L-rated tools and follow the unit’s A2L install notes – do not treat it like R-410A.
IMC 1107 / mfr
Refrigeration & Refrigerant

Refrigerant line sizing and support

Line sizes come from the manufacturer’s charts by capacity and equivalent length to keep oil return and capacity – undersized suction lines kill performance.

Rule of thumbSize line sets off the manufacturer’s chart by length and tonnage, and slope for oil return.
IMC 1101 / mfr
Refrigeration & Refrigerant

Line set insulation and protection

The suction line must be insulated, and both lines protected where exposed to sun, physical damage, or UV, to hold capacity and prevent sweating.

Rule of thumbInsulate the suction line and UV-protect line sets on the roof or south wall.
IMC 1101 / mfr
Refrigeration & Refrigerant

Evacuation and leak testing

Systems must be pressure-tested for leaks and evacuated to remove moisture and non-condensables before charging, per good practice and the manufacturer.

Rule of thumbPressure-test, then pull a deep vacuum before charging – moisture in the system causes failures.
IMC 1104
Refrigeration & Refrigerant

Refrigerant piping in ducts/plenums

Refrigerant piping is restricted in ducts, plenums, and shafts and where a leak could enter occupied air; follow ASHRAE 15 and the mechanical code limits.

Rule of thumbDo not run refrigerant lines through return plenums where a leak could reach breathing air.
IMC 1101 / listing
Refrigeration & Refrigerant

Condensing unit clearances and airflow

Outdoor condensing units need the manufacturer’s service and airflow clearances so the coil is not recirculating hot air or blocked by walls and fences.

Rule of thumbGive the condenser its listed clearances – crowding it with a fence spikes head pressure.
IMC 1101 / UMC 1100
Refrigeration & Refrigerant

Verify code – refrigerant rules changing

Refrigerant rules are changing fast with the A2L transition; the IMC, UMC, ASHRAE 15/34 editions, and local amendments differ – confirm what is adopted.

Rule of thumbThe A2L/refrigerant rules are in flux – verify the adopted edition and local amendments with the AHJ.
IFGC 402 / NFPA 54
Gas Piping & Appliances

Gas pipe sizing by longest length

Gas piping is sized from the code tables using the total connected load, the longest run to the farthest appliance, and the pipe material and pressure.

Rule of thumbSize off the longest-length method by BTU load and material – not by guessing pipe size.
IFGC 408 / NFPA 54
Gas Piping & Appliances

Sediment trap (drip leg) at appliances

A sediment trap (dirt/drip leg) is required at the connection to most appliances (furnaces, water heaters, boilers) to catch debris before the gas control.

Rule of thumbAdd a drip leg at each appliance – ranges, dryers, and outdoor grills are the usual exceptions.
IFGC 409 / NFPA 54
Gas Piping & Appliances

Appliance shutoff valve within reach

Each appliance needs an accessible manual shutoff valve in the same room, within about 6 ft of the appliance, ahead of the connector.

Rule of thumbPut a shutoff in the same room within 6 ft – upstream of the flex connector.
IFGC 411 / NFPA 54
Gas Piping & Appliances

Appliance connectors (flex) rules

Listed appliance connectors must be the right length (commonly 3 ft, up to 6 ft for ranges/dryers), not concealed, not run through walls/floors, and not reused.

Rule of thumbShort, listed, exposed connector only – never through a wall or reused from the old unit.
IFGC 310 / NFPA 54
Gas Piping & Appliances

CSST bonding

Corrugated stainless steel tubing (CSST) must be electrically bonded (traditional yellow CSST commonly with a #6 copper bond) per the manufacturer and NEC to reduce lightning damage.

Rule of thumbBond CSST per the manufacturer – usually a #6 bond clamp near the meter; black-jacket types differ.
IFGC 406 / NFPA 54
Gas Piping & Appliances

Gas piping pressure test

New gas piping is pressure-tested (commonly at least 3 psi, or 1.5x working pressure, held for the required time) before it is put in service and before appliances are connected.

Rule of thumbTest the rough gas pipe (often 3 psi for 10-15 min) and isolate appliances from the test.
IFGC 410 / NFPA 54
Gas Piping & Appliances

Regulator venting

Line-pressure regulators must vent to a safe outdoor location or use a listed vent-limiting device, and the vent must be protected from blockage and weather.

Rule of thumbVent regulators outdoors or use a listed vent limiter – keep the vent screen clear of insects.
IFGC 404 / NFPA 54
Gas Piping & Appliances

Piping materials and protection

Gas piping must be an approved material (black steel, listed CSST, or approved copper for some gases), protected from corrosion and physical damage, and properly supported.

Rule of thumbUse approved pipe, keep it off the ground/corrosive contact, and support it at code intervals.
IFGC 404.9 / NFPA 54
Gas Piping & Appliances

Protection where piping penetrates

Gas piping through concrete, masonry, or where it can be struck needs sleeving, coating, or striker plates so it is not abraded or punctured.

Rule of thumbSleeve or plate gas pipe through walls and slabs – protect it like water pipe, plus corrosion.
IFGC 415 / NFPA 54
Gas Piping & Appliances

Piping in concealed and prohibited locations

Gas piping cannot run through certain concealed spaces without meeting rules (no fittings in some concealed locations, protection in solid partitions), and not in air ducts.

Rule of thumbNo gas piping inside supply/return ducts, and limit concealed fittings per the code.
IFGC 621 / NFPA 54
Gas Piping & Appliances

Unvented room heaters restrictions

Unvented gas room heaters are prohibited in many locations (bedrooms, bathrooms) and by many jurisdictions entirely, and have input and oxygen-depletion-sensor requirements.

Rule of thumbUnvented heaters are banned in bedrooms/baths and by many AHJs – confirm before installing.
IFGC 501 / NFPA 54
Gas Piping & Appliances

Appliance venting required by type

Fuel-gas appliances must be vented per their category and listing; only appliances specifically listed as unvented may be installed without a vent.

Rule of thumbVent every gas appliance except those specifically listed as unvented – and honor local bans.
IFGC 303 / NFPA 54
Gas Piping & Appliances

Appliance clearances to combustibles

Gas appliances must keep their listed clearances to combustibles, or use listed reduced-clearance protection, and be installed on approved floors and supports.

Rule of thumbHonor the nameplate clearances to combustibles – reduced clearances need listed shielding.
IFGC 306 / NFPA 54
Gas Piping & Appliances

Appliance access and service

Gas appliances need the same access and working space as other mechanical equipment for service, inspection, and replacement.

Rule of thumbLeave service access at every gas appliance, same as any other equipment.
IFGC 621 / listing
Gas Piping & Appliances

Combustion products and CO safety

Vent connectors and appliances must be maintained to prevent spillage of combustion products; CO alarms are required in dwellings with fuel-fired appliances or attached garages.

Rule of thumbVerify no spillage at the draft hood and confirm CO alarms are installed and working.
IFGC / UMC / NFPA 54
Gas Piping & Appliances

Verify code – IFGC vs NFPA 54 vs local

Fuel-gas rules come from the IFGC or NFPA 54 depending on the jurisdiction, with local amendments (notably on CSST bonding and test pressures); confirm what applies.

Rule of thumbConfirm whether IFGC or NFPA 54 governs and check local amendments before final gas work.
IMC 1004 / ASME
Boilers & Hydronics

Boiler pressure-relief valve required

Every boiler needs an ASME-rated pressure (or pressure/temperature) relief valve sized to the boiler input, with no valve between it and the boiler.

Rule of thumbRelief valve sized to the boiler, no shutoff in between – it is the primary safety device.
IMC 1004 / mfr
Boilers & Hydronics

Relief discharge piping

The relief discharge must be full-size, run to a safe location (commonly terminating within about 6 in of the floor or to an approved point), and not be trapped or valved.

Rule of thumbFull-size discharge to a safe point near the floor – no reducer, no trap, no valve.
IMC 1009 / mfr
Boilers & Hydronics

Expansion tank on hydronic systems

Closed hydronic systems need a properly sized expansion tank to absorb water expansion and keep system pressure in range as temperature changes.

Rule of thumbSize and locate the expansion tank correctly – a waterlogged tank causes relief-valve weeping.
IMC 1008 / ASME
Boilers & Hydronics

Low-water cutoff

Boilers (especially steam and larger hot-water boilers) require a low-water cutoff to shut off the burner if the water level or flow drops too low.

Rule of thumbConfirm a working low-water cutoff – dry-firing a boiler is catastrophic.
IMC 1006 / listing
Boilers & Hydronics

Boiler clearances and mounting

Boilers need the listed clearances to combustibles, service access on required sides, and a proper noncombustible base or floor protection where required.

Rule of thumbSet boilers on an approved base with listed clearances and service room on the burner side.
IMC 1010 / mfr
Boilers & Hydronics

Hydronic piping and isolation

Hydronic piping must be sized for flow, supported, and provided with isolation valves, air elimination, and drains for service.

Rule of thumbAdd isolation valves, air vents, and drains so the system can be serviced and purged.
IMC 1003 / gauge
Boilers & Hydronics

Boiler gauges and controls

Boilers need pressure and temperature indication and operating/limit controls so status is visible and the burner shuts off on high limit.

Rule of thumbVerify the pressure/temp gauge and high-limit control are present and working.
IMC 1005 / backflow
Boilers & Hydronics

Makeup water and backflow protection

Boiler fill/makeup water connections need a pressure-reducing valve and backflow protection so treated boiler water cannot siphon back into the potable supply.

Rule of thumbProtect the boiler fill with a backflow preventer – especially if the system is chemically treated.
IMC 1012 / mfr
Boilers & Hydronics

Hydronic floor and radiant systems

Radiant and hydronic distribution needs proper temperature control (mixing valves), pressure testing, and materials rated for the fluid temperature and pressure.

Rule of thumbUse a mixing valve to protect radiant tubing and pressure-test before covering it.
IMC 1001 / UMC 1000
Boilers & Hydronics

Verify code – boiler rules and ASME

Boiler and pressure-vessel rules pull in ASME and sometimes separate state boiler regulations beyond the IMC/UMC; confirm the local boiler authority requirements.

Rule of thumbMany states have a separate boiler inspector – confirm ASME stamping and local boiler rules.
NEC 440.14
Electrical for HVAC

Disconnect within sight of equipment

HVAC condensing units and equipment need a disconnecting means within sight and readily accessible, within 50 ft of the equipment (not behind the unit where it is blocked).

Rule of thumbDisconnect within sight and 50 ft, on an accessible side – not hidden behind the condenser.
Nameplate / NEC 440
Electrical for HVAC

Size circuit to MCA, not just breaker

Branch-circuit conductors are sized to the equipment’s minimum circuit ampacity (MCA) on the nameplate, not simply to the breaker size.

Rule of thumbPull wire to the MCA on the nameplate – the breaker follows MOCP, the wire follows MCA.
Nameplate / NEC 440
Electrical for HVAC

Max overcurrent protection (MOCP)

The breaker or fuse cannot exceed the maximum overcurrent protection (MOCP / max fuse) on the nameplate – going bigger to stop nuisance trips is a violation.

Rule of thumbNever exceed the nameplate MOCP – a bigger breaker is not the fix for a real fault.
NEC 440.22
Electrical for HVAC

HACR and short-circuit protection

Use the type and rating of overcurrent device the nameplate specifies (often HACR-rated breakers) to protect the compressor and circuit.

Rule of thumbMatch the breaker type to the nameplate (HACR where required) – not just the amperage.
NEC 210.8(F)
Electrical for HVAC

GFCI for outdoor HVAC outlets

Outdoor outlets serving dwelling HVAC equipment require GFCI protection under recent NEC editions, which has caused nuisance-trip issues with some equipment.

Rule of thumbRecent NEC requires GFCI on the outdoor HVAC circuit – verify the adopted edition, some jurisdictions amend it.
NEC 400 / 440
Electrical for HVAC

Flexible whip / liquidtight connection

The final connection to a condensing unit is commonly a listed flexible whip (liquidtight) of limited length to allow for vibration and service.

Rule of thumbUse a short listed liquidtight whip at the condenser – support it and keep it out of water.
NEC 210.63
Electrical for HVAC

Service receptacle at equipment

A service receptacle within 25 ft on the same level is required for HVAC/refrigeration equipment, not fed through the equipment disconnect.

Rule of thumbSame 25-ft service receptacle rule applies – separate from the unit’s power.
NEC 250 / mfr
Electrical for HVAC

Equipment grounding and bonding

HVAC equipment, whips, and CSST gas systems must be grounded and bonded per the NEC and manufacturer to control faults and lightning energy.

Rule of thumbBond and ground the unit and the gas system – do not rely on the pipe threads.
NEC 424 / 424.19
Electrical for HVAC

Electric heat and disconnects

Electric furnaces, duct heaters, and heat strips have their own disconnect and overcurrent rules and load calculations separate from the cooling side.

Rule of thumbHeat strips add load and need their own disconnect/overcurrent – include them in the service calc.
NEC / local
Electrical for HVAC

Verify code – NEC edition and amendments

Electrical rules follow the adopted NEC edition and local amendments (GFCI, AFCI, disconnect specifics vary by cycle); confirm what your jurisdiction enforces.

Rule of thumbConfirm the adopted NEC edition – GFCI/disconnect rules change and are often locally amended.
ACCA Manual J
Sizing & Load

Do a Manual J load calculation

Equipment must be sized to a room-by-room heating and cooling load calculation (ACCA Manual J or equivalent), which the energy code and many AHJs require in writing.

Rule of thumbRun a Manual J – not a rule of thumb – and keep the printout for the permit.
ACCA Manual S
Sizing & Load

Select equipment with Manual S

After the load, equipment is selected with ACCA Manual S so capacity matches the load at design conditions – not just nominal tonnage on the label.

Rule of thumbMatch capacity to the Manual J load with Manual S – nameplate tons are not the delivered capacity.
ACCA Manual D
Sizing & Load

Design ducts with Manual D

Duct systems are designed with ACCA Manual D to deliver each room’s airflow at the equipment’s available static pressure.

Rule of thumbDesign the duct to Manual D – the right box on the wrong duct still underperforms.
ACCA Manual T
Sizing & Load

Select registers with Manual T

Supply registers and returns are selected (ACCA Manual T) for throw, spread, and noise so the design airflow actually mixes the room.

Rule of thumbPick registers for throw and noise, not just to cover the hole.
Rule of thumb + caveat
Sizing & Load

Tonnage rule of thumb – use with caution

The old 400-600 sq ft per ton guideline is only a sanity check; tight, well-insulated, or extreme-climate homes vary widely and oversizing hurts comfort and humidity.

Rule of thumb400-600 sq ft/ton is a gut check only – always confirm with a real load calc.
Manual J
Sizing & Load

Oversizing hurts dehumidification

Oversized cooling short-cycles, so it cools fast but does not run long enough to remove humidity, leaving the house cold and clammy.

Rule of thumbBigger is not better – an oversized AC leaves the house cold and damp.
Manual J
Sizing & Load

CFM per ton airflow target

Cooling systems are typically set up around 350-450 CFM per ton (often 400) of airflow across the coil; verify the target for the equipment and climate.

Rule of thumbAim near 400 CFM per ton across the coil – low airflow freezes coils, high airflow kills dehumidification.
Manual J / mfr
Sizing & Load

Design conditions drive the load

Loads are calculated at the local outdoor design temperatures (not record extremes) and target indoor conditions – using the wrong design temps oversizes the system.

Rule of thumbUse the local design temperatures, not the hottest day ever recorded, or you will oversize.
IECC / Manual J
Sizing & Load

Energy code requires the calc

The energy code (IECC) and many jurisdictions require documented load calculations and equipment sizing as a condition of the mechanical permit.

Rule of thumbExpect the AHJ to ask for the Manual J – have it ready at permit time.
ACCA / local
Sizing & Load

Verify code – which standards are referenced

Codes reference the ACCA manuals (J, S, D, T) but the required editions and documentation differ by jurisdiction; confirm what must be submitted.

Rule of thumbConfirm which ACCA manuals and editions your AHJ requires submitted with the permit.
IECC / IMC 403
Special / IAQ / Commercial

Economizers on larger units

The energy code requires air-side (or water-side) economizers on cooling systems above a capacity threshold in many climate zones, to use outdoor air for free cooling.

Rule of thumbLarger commercial units often need an economizer by the energy code – verify the threshold and climate zone.
IECC
Special / IAQ / Commercial

Energy-code duct sealing and insulation

The IECC sets duct-leakage limits (with testing), insulation R-values, and equipment efficiency minimums that go beyond the mechanical code.

Rule of thumbDuct leakage testing and R-values are energy-code items – plan for the blower/duct test.
IMC 507 / IBC
Special / IAQ / Commercial

Type I kitchen hoods (grease)

Commercial cooking that produces grease-laden vapor needs a listed Type I hood with grease filters, a fire-suppression system, and dedicated grease-duct exhaust.

Rule of thumbGrease-producing cooking gets a Type I hood with suppression and welded grease duct – specialist territory.
IMC 507
Special / IAQ / Commercial

Type II hoods (heat and moisture)

Cooking or equipment that produces heat, steam, or odors but not grease uses a Type II hood, with simpler exhaust than Type I.

Rule of thumbDishwashers and ovens without grease use a Type II hood – lighter duty than Type I.
IMC 506
Special / IAQ / Commercial

Commercial kitchen exhaust duct

Grease ducts must be liquid-tight welded steel, sloped, with cleanouts and clearances or an enclosure, and terminate at the required distance from the roof and openings.

Rule of thumbGrease duct is welded, sloped, cleanout-equipped, and fire-rated enclosed – not standard duct.
IMC 1101 / IIAR
Special / IAQ / Commercial

Commercial and ammonia refrigeration

Large commercial refrigeration (supermarket, industrial, ammonia) has specialized machinery-room, detection, relief, and code requirements beyond comfort cooling.

Rule of thumbIndustrial and ammonia systems are specialist-engineered – do not apply comfort-cooling rules.
ASHRAE 62 / IAQ
Special / IAQ / Commercial

Indoor air quality and filtration

IAQ provisions cover minimum filtration (MERV), outdoor-air delivery, and control of moisture and contaminants; higher-filtration systems must be designed for the added static.

Rule of thumbUpgraded filtration (higher MERV) adds static – design the fan/duct for it or airflow drops.
Local / AHJ
Special / IAQ / Commercial

Verify code – special systems need specialists

Commercial kitchens, labs, healthcare, industrial refrigeration, and smoke-control systems carry specialized codes and often require engineered, stamped designs.

Rule of thumbFlag special-occupancy and life-safety systems for an engineer and the AHJ – do not field-guess them.
No rules match that search. Try a different keyword or clear the category filter.

Powered by Trade Template Co.

More HVAC tools

Back-office, sorted

Contractor Estimate & Invoice Templates (Word, Excel & Google Sheets)

Pair code confidence with paperwork that gets you paid faster — itemized estimates, invoices, and proposals built for HVAC and every other trade.

TTC

Trade Template Co. builds back-office tools for trade businesses. This quick-reference is a plain-English recall aid, not a code-compliance tool or legal advice — always confirm against the currently adopted IMC or UMC, the adopted fuel-gas code (IFGC or NFPA 54), and your local AHJ.

Your HVAC Contractor Portal

Every HVAC calculator, template, and resource, in one place.

Back to the HVAC Contractor Portal